Legionella Testing | ISO, CDC Culture, qPCR

Analytical + Environmental / Legionella Testing and Analysis

Legionella Testing for Building Water Systems

Pace® provides Legionella testing and analysis for building water systems, cooling towers, potable plumbing, hot water storage and process water. Many Pace® laboratories are CDC ELITE and AIHA accredited, and we run four test methods: Legionella ISO culture, Legionella CDC culture, Legionella qPCR and Legiolert. Pace® is an independent provider, unaffiliated with water treatment vendors, so results are not influenced by a remediation interest. Sampling kits ship nationwide and Pace® Legionella Emergency Response Services can manage every aspect of an outbreak response.

Protect your employees and customers from preventable diseases while mitigating your business risks with Pace® Legionella testing services.

REACH OUT TO OUR EXPERIENCED STAFF WITH ANY QUESTIONS OR TO LEARN MORE.
Pace Scientist working in Laboratory

Legionella Test Methods: ISO Culture, CDC Culture, qPCR and Legiolert

Which Legionella Test Should You Use?

Suitable for
TAT*
Advantages
Disadvantages
Legionella ISO Culture
  • Compliance
  • Baseline testing and water management validation
  • Outbreak forensics
  • 7 days**
  • Considered the gold standard in the industry
  • Highly accurate
  • Capable of detecting 20 species of Legionella, including 16 serogroups of L. pneumophila
  • Longer TAT required than all other methods. (Can be paired with qPCR to begin initial outbreak forensics.)
    Legionella MICA®
  • Baseline testing, water management program risk assessment, and validation
  • Post-remediation effectiveness verification
  • Time-constrained outbreak forensics and case investigations
  • Cooling towers and other high-background samples
  • 3 days
  • Fast, culture-based results; often paired with Legionella Culture for more detailed analysis
  • Detects only live bacteria
  • Results reported in CFU/mL for easy comparison to other culture methods
  • AI-assisted counting performs well in samples with high levels of background bacteria
  • Can only detect Legionella pneumophila
  • Can detect but not identify L. pneumophila serogroups (Can be paired with Legionella Culture for serogroup identification.)
  • Legionella CDC Culture
  • Compliance
  • Baseline testing and water management validation
  • Outbreak forensics
  • 7 days**
  • Highly accurate
  • Capable of detecting 20 species of Legionella, including 16 serogroups of L. pneumophila
  • Longer TAT required than Legionella qPCR. (Can be paired with qPCR to begin initial outbreak forensics.)
    Legionella qPCR
  • Baseline testing and water management validation
  • Time-constrained outbreak forensics
  • 1-2 days
  • Fast – often paired with Legionella Culture for more detailed analysis
  • Can detect all species of Legionella
  • Can only identify one serogroup of L. pneumophila – serogroup 1
  • Cannot indicate whether the bacteria was alive when the sample was collected
  • Legiolert
    Baseline testing and water management validation
    7 days
  • Little technical skills required to perform
  • Easy to interpret results
  • High number of false positives in non-potable water if lab SOPs do not control potential for cross-reactivity
  • Can only test for Legionella pneumophila
  • * Turnaround time. All TATs quoted are industry standard. Some scenarios may allow for faster turnaround. Talk with your Pace® representative if faster results are needed.

    ** Regulatory requirements in some states, such as New York and Connecticut, may extend TAT times. Talk with your Pace® representative for details.

    Why Test For Legionella

    Legionella bacteria pose a serious health risk, especially in large plumbing systems and cooling towers where they can grow and spread. They can cause Legionnaires’ disease—a severe form of pneumonia—as well as Pontiac fever, a milder flu-like illness. Both can be dangerous, particularly for individuals with weakened immune systems.

    Proactive Legionella testing helps prevent outbreaks, protect occupants, and ensure water systems are safe and compliant. With comprehensive testing and analysis, Pace® helps organizations detect risks early, safeguard public health, and maintain regulatory confidence.

    Legionella Regulations: CMS, Joint Commission, OSHA and State Rules

    Legionella testing in water systems is essential for protecting public health and reducing organizational risk. The Centers for Medicaid and Medicare Services (CMS) has rules for healthcare facilities.

    Facilities that accept Medicare and Medicaid must implement water management policies. These policies help reduce the risk of Legionella and other harmful germs. In 2022, the Joint Commission set new standards for accredited organizations. This includes hospitals and nursing care centers to tackle Legionella.

    Various states have their own requirements. New York requires hospitals and healthcare facilities to monitor and control Legionella.

    Whereas, New Jersey needs policies for healthcare facilities and buildings with large water systems. The CDC provides guidelines for preventing Legionnaires’ disease. OSHA has standards for workplaces with potential Legionella contamination. States may also regulate other hot spots, such as New York’s requirement for cooling tower testing to reduce increased risk.

    Compliance

    Many organizations, like those in healthcare, must have water management policies. These help reduce the risk of Legionella and other harmful germs. However, testing is not always required but can play an important role in validating compliance.

    Water Safety Management Validation

    Even if the law does not require testing for Legionella, baseline testing can help ensure water safety. Therefore, water sample collecting is important for places like hotels and recreational facilities.

    Reputation Management

    An outbreak of Legionnaires' disease linked to a company's facilities can harm its reputation. Therefore, could lead to lost business and other problems. Routine testing can help limit the risk of an outbreak. Therefore, if an outbreak does occur, testing can help identify the source.

    Industries We Serve

    Legionella testing is requested by healthcare facilities operating under CMS water management requirements and Joint Commission standards, hospitality and multifamily property operators, manufacturing and industrial sites with cooling towers, commercial building owners and facility managers, cruise and maritime operators, and water management program consultants.

    Water Treaters

    Water treaters and consultants are important for keeping water systems safe. They help prevent Legionnaires' disease by testing, monitoring, and managing water quality.

    Healthcare Facilities

    Nursing homes, long-term care facilities, and hospitals must keep patients safe. They should test regularly to prevent problems.

    Hotels and Resorts

    Regular testing in hotels and resorts can help prevent outbreaks, protect guests, and maintain the establishment’s reputation.  

    Cruise Ships

    Cruise ships have complex water systems, including potable water, showers, hot tubs and pools, that can amplify Legionella growth. Regular testing helps protect passengers and crew, prevent outbreaks, and keep amenities in service.

    Educational Institutions

    Universities and other educational institutions should test to ensure the safety of students, staff, and visitors.

    Commercial Buildings

    To ensure the safety of all occupants and visitors, regular testing for Legionella should be conducted in commercial buildings.

    Data Centers

    Data center water systems, such as cooling towers, can create an environment in which Legionella thrives. If you use evaporative cooling, you should test these systems regularly to prevent an outbreak.

    Government Buildings

    Government buildings, including those run by the General Services Administration (GSA), should test often. This helps prevent outbreaks and keeps health rules in check. It also protects public health.

    Legionella Reports and Turnaround

    Reports identify the method, the sample location, the analytical date and the result in the units your water management plan requires, with serogroup identification available on culture results. Sampling kits with the correct containers, neutralizers and chain of custody paperwork ship before your sampling event. qPCR results are available in hours. Culture results follow the incubation period the method requires. Contact the laboratory to confirm turnaround before you sample.

    Pace® Scientists discussing report results while standing in laboratory.

    Introducing MICA®: AI-Powered Legionella pneumophila
    Testing with Results in 3 Business Days

    When operational continuity depends on Legionella results, waiting 7 to 10 days for traditional culture can feel like an eternity. MICA® Legionella testing combines a specialized labeling chemistry with AI-powered analysis to detect and count live Legionella pneumophila in 48 hours with a report delivered in 3 business days. Unlike qPCR, which can detect DNA from both living and dead bacteria, MICA® is culture-based, so you get actionable results on viable organisms faster. In addition, MICA® is the only validated method for the detection of live Legionella pneumophila that can provide results in under 3 days, which sets it apart from viability qPCR.